Technical specification

3.3 MVA Resistive Load Bank — LB-3300

A container-grade, low-noise 3,300 kVA load bank engineered for continuous outdoor duty. Wide voltage and frequency compatibility makes it a drop-in test load for generator sets, UPS strings, transformers and microgrids across the UK and Europe.

Rated capacity
3,300 kVA
2,640 kW / 1,980 kVAr @ 0.8 PF
Test voltage
415 V
3-phase, 3/4 wire, 4,630 A
Frequency
50 Hz
Grid or genset
Loadbank type
Resistive / Reactive
Crestchic C7884 · 2024
Enclosure
10 ft × 8 ft 6 in
ISO container · RAL 7046 · 9,780 kg
Auxiliary supply
400 – 415 V
50 Hz · 3-ph · 50 A (utility 220–240 V 16 A)
Full spec sheet

Everything on the datasheet.

Electrical

  • Loadbank type: resistive / reactive
  • Test supply 415 V, 3-phase, 50 Hz, 3/4 wire
  • Rated capacity 3,300 kVA — 2,640 kW / 1,980 kVAr at 0.8 PF
  • Rated current 4,630 A continuous
  • Auxiliary supply 400 – 415 V, 50 Hz, 3-phase, 50 A
  • Utility supply 220 – 240 V, 16 A
  • Load-step resolution 1.66 kW / 1.96 kVAr at design voltage
  • 240 mm² Powerlock tails available at £20 per set of 4 cables per day

Enclosure & construction

  • 10 ft × 8 ft 6 in ISO-style container
  • Overall dimensions 2991 × 2438 × 2896 mm (L × W × H)
  • Weight 9,780 kg (21,561 lbs)
  • Finish RAL 7046 — Offshore CX
  • Lloyd's Register-certified container
  • Twistlock corners, bottom lift
  • IP55 control protection

Elements & cooling

  • Stainless steel finned resistor elements
  • 6 × forced-air cooling fans sized for continuous 3.3 MVA dissipation
  • Low-noise variant available for noise-sensitive sites

Environmental

  • Full output at 50 °C ambient
  • All-weather outdoor operation
  • Stackable when not in use for compact site storage
Range overview

2,000 – 3,300 kVA packaged loadbank range.

Our headline unit is the 3.3 MVA LB-3300. It sits inside a wider transportable range — useful when you're specifying multi-bank tests or need extra headroom for reactive load.

RatingReal power @ 0.8 pfReactive power @ 0.8 pfApprox. weight
2000 kVA1,600 kW1,200 kVAr8,000 kg
2500 kVA2,000 kW1,500 kVAr8,500 kg
3000 kVA2,400 kW1,800 kVAr9,500 kg
3300 kVA2,640 kW1,980 kVAr10,000 kg
Technical detail

Line-by-line datasheet.

Every parameter from the manufacturer's spec sheet, grouped so your commissioning engineer can find what they need at a glance.

Power & connection

Loadbank type
Resistive / reactive
Test supply voltage
415 V
Test supply frequency
50 Hz (single-frequency rating)
Phases / wires
3-phase, 3/4 wire star
Rated current
4,630 A
Power factor
0.80
Nominal rating
2,640 kW / 3,300 kVA / 1,980 kVAr
Load-step resolution
1.66 kW / 1.96 kVAr at design voltage
Voltage tolerance
+5% short-term
Load tolerance
±5%
Load connections
M16 copper busbars, Powerlock tails
Load switching
AC-1, 3-pole AC contactors

Elements & reactors

Elements
80/20 Nickel Chrome resistance wire
Reactors
Iron core, Class F
Insulation test
500 V
Protection
Element thermal sensor, air-flow switch, reactor thermal sensor, fan overload, E-stop

Auxiliary supply

Auxiliary supply
400 – 415 V, 50 Hz, 3-phase, 50 A
Utility supply
220 – 240 V, 16 A
Control voltage
Selectable — Test (<480 V) or Auxiliary

Cooling & environment

Cooling method
Forced-air, vertical exhaust
Air flow
~1,440 m³/min
Max ambient
+50 °C / +122 °F
Min ambient
-20 °C / -4 °F
Max humidity
95% RH
Altitude
<500 m a.s.l.

Enclosure

Type
10 ft × 8 ft 6 in ISO-style container
Serial number
C7884
Year of manufacture
2024
Weight
9,780 kg (21,561 lbs)
Finish
RAL 7046 — Offshore CX
Control IP rating
IP55
Lifting
Twistlock corners (bottom lift)
Country of origin
United Kingdom

Dimensions & airflow

Length
2,991 mm (117 ¾")
Width
2,438 mm (96")
Height
2,896 mm (114 1/64")
Cool-air intake
Left & right side louvres
Hot exhaust
Top-mounted, vertical
Fan array
6 × forced-air fans (FAN 0 – FAN 5)

Control systems

Primary control
MCS — PC software or LC80 terminal
Multi-bank control
Extendable across multiple loadbanks
Back-up control
KCS manual controller (optional)
Extension cables
50 m or 100 m runs (10 m extend lead)
Comms
Fibre media converter, 110–240 V 50/60 Hz 1-ph supply
Optional extras
Modbus, ASS180/181/182 monitoring, Windfarm & Extreme Temp packages
Airflow & layout

Cool air in the sides, hot air out the top.

Cool-air intake

Side louvres draw ambient air across all six fans — no obstruction needed at the front or rear.

Hot-air exhaust

Vertical top exhaust throws heat straight up, so the unit can sit close to walls or other plant.

Site clearance

Plan on 1 m access to the control-side doors and unobstructed sky above the exhaust hood.

Need it fully operated?

Add on-site engineers when you book and we'll handle installation, commissioning and live operation for you — up to a 12-hour shift per day.

Build a quote